LANmark-OF Aggregation Assembly MTP/F-4XDLC

Description
- Factory terminated fibre assembly
- Fibre assembly with Female MTP towards 4x uniboot DLC connectors
- Female MTP connector for connecting to QSFP+ transceiver on switch
- Uniboot DLC connectors for patching on front of patch panel
- Aggregation of 4X 10G channels on patch panel into 1x 40G port on switch
- Fibre type: OM3 and OM4
- 8 core
- Low loss connectivity performance: max of 0,3 dB per connection

Description
- Factory terminated fibre assembly
- Fibre assembly with Female MTP towards 4x uniboot DLC connectors
- Female MTP connector for connecting to QSFP+ transceiver on switch
- Uniboot DLC connectors for patching on front of patch panel
- Aggregation of 4X 10G channels on patch panel into 1x 40G port on switch
- Fibre type: OM3 and OM4
- 8 core
- Low loss connectivity performance: max of 0,3 dB per connection
Standards
International : ISO/IEC 11801:2002/Amd 1:2008/Cor 1:2008Description
Construction
A round cable with a diameter of 3,65 mm is terminated on one side with a female MTP*-connector. The other side is terminated as a fan-out with uniboot duplex LC connectors. The round fan-out legs contain 2 fibres. The lengths between the fan-out point and each uniboot connector is equal and typically 1m (fan out A) or 2m (fan out C). The length between the MTP-connector and the fan-out point is variable and can be increased in steps of 1 m.
The cable features a small bend radius of 40mm and has bend insensitive fibres inside.
The cable is flame non propagation (IEC 60332-1) and fire non propagation (IEC 60332-3).
Application
The assembly allows to aggregate 4X 10G channels from the front of a patch panel into 1x 40G port on a switch.
The female MTP-connector fits with the male MTP connector inside the 40G QSFP+ port of the switch.
Performance
The MTP connector has a low loss performance. Typical value for the insertion loss for the low loss MTP-MTP connection is 0.125 dB. The limit value is 0.3 dB measured according to standard IEC 61300-3-45.
Consistent quality
In order to produce high quality, reliable pre-terminated multi-fibre cables, there are a number of physical characteristics that must be addressed. Therefore, all LANmark-OF Pre-Terms are fully terminated and tested in a quality assured factory environment. They are delivered with these test results.
* MTP is a trade name of US Conec
Characteristics
Construction characteristics | |
---|---|
Fiber optic type | OM3 50/125 |
Dimensional characteristics | |
Nominal outer diameter | 3.65mm |
Mechanical characteristics | |
Mechanical resistance to impacts | 10 impacts of 1 N.m |
Crush resistance (IEC 60794-1-E3) | 50N/cm |
Usage characteristics | |
Minimum static operating bending radius | 40mm |
Storage temperature, range | -20 .. 60°C |
Flame retardant | IEC 60332-1 |
Operating temperature, range | 0 .. 60°C |
Fire retardant | IEC 60332-3 |